Machine on ESP32-S3

Status: v0.1 — review answers folded in, 2026-07-31. Deliberately short — structure over detail. Nothing implemented yet.

Goal​

Deploy the pstop_c machine role on the same ESP32-S3 platform as the remote: a self-contained box that bonds remotes, runs the safety decision dual-core, and actuates the robot's stop circuit through relays. The pure software machine (host/machine_app_runner) remains fully supported — same library, same wire protocol, same config semantics; this is a second machine form factor, not a replacement.

Reused from the remote (unchanged infrastructure)​

  • Hardware: Waveshare ESP32-S3-ETH (PoE), same enclosure family.
  • Connectivity: microlink (Tailscale/WireGuard/DERP), eth → wifi supervised uplinks. Own tailnet identity derived from eFuse MAC, prefix distinguishes the role: machn-01<mac24> (remotes keep pstop-).
  • Platform services: NVS-persisted settings + admin UI, boot-count safety ladder, direct OTA (/admin/api/ota), /state.json telemetry (with fw_ver/fw_sha), reset-history, panic log.
  • pstop_c untouched, as always: the machine role is what the library already provides; everything below is the shell around it.

Dual-core RX lockstep (mirror of the remote's TX lockstep)​

The remote's pattern: two cores independently encode, byte-compare, transmit only on agreement. The machine inverts it:

  • Each core runs its own pstop_c machine instance (own state, own remotes table) and independently decodes + validates every received datagram and computes (verdict, reply bytes).
  • A comparator (same 100 ms tick discipline as the remote) compares the two cores' verdicts AND reply bytes. Agree → actuate relays to the agreed state, send the reply. Disagree → treat as internal fault: both relay outputs commanded open (STOP), reply withheld (the remote sees silence and stops, exactly like a remote-side mismatch), mismatch counter incremented (purple-equivalent indication, persistent-only per the current ring policy).
  • Liveness (check_heartbeats) runs per core on the shared monotonic clock; a timeout verdict must also agree before it opens the relays — with the caveat that either core alone opening its relay already stops the robot (see below), so disagreement is never less safe.

Relay output + feedback (replaces the remote's button inputs)​

[DESCOPED 2026-08 — feedback OFF by default, REVERSIBLE.] The relay feedback / read-back described in this section is compiled out by default via the Kconfig option CONFIG_MACHN_RELAY_FEEDBACK (default n), pending a new machine hardware revision whose wiring makes the divider voltages unreadable. The relay drive (below) and the series de-energize-to-safe stop are unchanged. Set the Kconfig to y to restore feedback. Full detail + safety-case impact: docs/design/relay_feedback_descope.md.

Two opto-isolated relays, contacts wired in series in the robot's stop circuit — either core alone can break the circuit:

  • Core 0 drives relay A, core 1 drives relay B (one GPIO each through opto-isolated drivers, reusing the remote's E-stop loop pins). Energized = circuit closed = robot may run; de-energized = STOP. Power loss, brownout, reset, or a hung core all fail to STOP.
  • Feedback = output-voltage sensing: a resistor divider on each relay's switched output, read as a digital input by BOTH cores. After any commanded transition the observed voltage must match within RELAY_FEEDBACK_MS (TBD from relay switching time) and is also checked continuously at every comparator tick.
  • Fault semantics — nothing latches. Transient conditions (a momentary core disagreement, a momentary loss of remote signal) already self-recover exactly as on the remote: the comparator withholds/opens for the duration and resumes when agreement returns. A feedback contradiction (e.g. output still live after commanding open — welded contact / shorted driver) raises a persistent relay-fault indication for as long as the condition is observed: telemetry flag, fault counter, and the machine keeps both outputs commanded open. Safety does not depend on latching — the series partner relay breaks the circuit — but the indication persists so a single-channel box gets serviced; it clears by itself when feedback returns to sanity.

Reporting to the ROS2 computer​

The ESP32 machine replaces the runner's decision role but the robot computer still needs live state. Two channels, both read-only:

/state.json gains machine-role fields: robot verdict, restart state, arming owner, per-remote table (bonded/heartbeat age), relay commanded/observed states, mismatch + fault counters. A thin ROS2 node (successor of the archived protective_stop_node) polls it at 5 Hz and republishes as topics — robot_status, relay_state, fault. No new firmware surface; no UDP stream.

The stop circuit itself is the relay chain — the ROS2 reporting path carries no safety responsibility.

Fleet / OTA policy (config-gated, per decision)​

  • The machine runs the same fleet check-in code but registers with device_type: "machine" in the check-in payload (new field, remotes implicitly "remote").
  • Server-side enforcement (required, management-console work): the console must refuse to assign remote firmware to device_type != remote — machines get their own image lineage or nothing. This needs a handoff item to the console session before any machine unit ships.
  • Belt-and-braces on the device: machine builds set auto_update default off, and the OTA-apply path verifies the incoming image's project name (machn_machine vs pstop_remote in the app descriptor) and rejects a mismatch regardless of what the server says.
  • Direct OTA (/admin/api/ota) remains the recovery path, same as today.

Config​

The machine.toml knobs move to NVS + admin UI (same pattern as the remote's settings): admission allow/denylist (/api/admission, optional — who may bond; re-arm authority is each remote's own announced role), max_missed_heartbeats, min_stop_ms (→ library delay_between_stop_ms), machine_device_id, listen port. Persisted, live-applied where safe.

Out of scope for v1​

Certification argumentation; multi-machine coordination (remote side already handles up to 4 machines — an ESP32 machine is just one of them); LED ring on the machine box (onboard RGB only for v1, TBD); console MACHINES-tab integration beyond the existing announce.

Resolved in review (2026-07-31)​

  1. Relay: opto-isolated module; feedback via resistor divider on the switched output read as digital IO. Exact part TBD during hardware pass; RELAY_FEEDBACK_MS set from its switching time.
  2. No fault latching: indication only Revised 2026-07-31 after bench test (disconnected feedback looked fully green): a feedback contradiction persisting ≥ ~1 s now stops the robot — both relays open, replies STOP, re-arming refused while the fault is present. Still no latch: clears with the fault; re-arm requires a fresh remote gesture. Named telemetry: relay_fault_a/b (consecutive contradiction ticks) + relay_stop in /state.json; commanded/ observed in e_hi*/e_lo*.
  3. ROS2 reporting: poll /state.json at 5 Hz; no UDP stream.
  4. Arming: remote gestures only — the machine box has no arm input.
  5. Naming: remotes keep pstop; machines use machn.